UNLV Hotel College Academic Building, Las Vegas, NV

UNLV Hotel College Academic Building, Las Vegas, NV

Project Description:

TMCx Solutions, LLC was contracted by State of Nevada to provide LEED Enhanced commissioning for the UNLV Hotel College Academic Bldg project. This project is a 96,523 square foot 4-story space located at 1830 E. Sahara Ave. The project is located in the Cnetral portion of the UNLV Campus. It shares a strong relationship with the entry to the Lied Library.

Scope of Work:

This project was Commissioned for Fundamental and Enhanced Commissioning for LEED Certification. Project was designed to LEED Silver.

Systems:

  • Chilled Water System
  • Heating Water System
  • Air Handling System
  • Ventilation System
  • Terminal Units
  • Plumbing Units
  • Electrical

Project Snapshot

  • Owner:  NV State Public Works
  • Project Size: 96,523 sq. ft..
  • Construction Cost:  $33.2M
  • GC:  McCarthy Building Construction
  • Year of Completion:  2018

Challenges and Successes

  • ISSUE: hen we failed CT-1 fan 2 VFD failed CT-2 started ok, but CT-1 was allowed to continue to run with CT-2 operating and one condenser water pumps. CT-1 should have been disabled and only CT-2 should have been running. CWS temperature rose to 85 deg F where 75 deg F SP was called for. CT-1 VFD-1 failed and both tower valves were allowed to remain OPEN.

    RESOLUTION: Honeywell re-programmed system fail over SOO so that tower valves close when system is disabled.

  • ISSUE: Ahu-1 thru 4 Supply fan wall and relief fan wall current sensors may need to be relocated for better individual fan status/alarm, may need to be relocated due to close proximity for each other.

    RESOLUTION: Ahu-1 thru 4 Supply fan wall and relief fan wall current sensors have been relocated for better individual fan status reporting.NV State Public Works