Canoga Park High School

Lausd Canoga Park High School Modernization

LAUSD Canoga Park High School Modernization

Project Description:

The Canoga Park High School gymnasium was modernized with new HVAC, electrical, plumbing, and structural systems to meet current code

Scope of Work:

TMCx was retained by the District to provide commissioning services for new HVAC and EMS equipment and systems to replace deteriorated HVAC mechanical systems. Services include design review and comment, submittal review and comment, and construction and post – occupancy

Project Snapshot

  • Owner: LA Unified School District
  • Project Size: 30,000 sq. ft.
  • Construction Cost: $3M
  • GC: Prime Axix
  • Year of Completion: 2019

Systems:

  • Central Utility Plant
  • Air handling Units
  • VAV Terminal Units, Exhaust)
  • Domestic Heating Hot Water
  • Electrical Systems

Challenges and Successe

  • Issue: During functional testing it was found that the space pressure pneumatic tubing wasinstalledin thereturn ductwork through the fire damper and just resting in the return grill. The outside air pressurepneumatic tubing to reference outsideairpressure is just lying in the return plenum. With the currentarrangement the space is unable to build any pressure when the unit is in economizer mode (full outsideair) thus not allowing the exhaust fans to operate correctly

          Resolution: the tubing was reinstalled and verified to operate properly.

  • Issue: During functional testing it was found that the BAS is not currently on the LAUSD server. With thisnot being completed functional testingcouldnot be completed until the project is on the server to verifyoccupancy schedule, alarms and the building graphics.

          Resolution: the controls contractor updated the database to the District and functional testingproceeded.